Detail NR1 ELEC/INST RM/KL/CM
2024-09-30
393-RF6
Wahyu Adi Triono
Problem: Service motor
Action:
Dismantle motor from site, service motor at work shop. Measure with megger result resistance R-S-T 2000 M Ohm. Refill oil 320, test on motor no load, measure ampere around 3.7 A - 3.5 A ( PENY & ADI & FIRMAN )

Status: done