Detail NR1 ELEC/INST RM/KL/CM
2024-12-06
473-FN4
Wahyu Adi Triono
Problem: High vibration 6 mm/s
Action:
Check at local measure vibration free and load side motor. Add grease 15 times for free and load side motor measure vibration result 3.4 mm/s ( AGUS & MUHAIMIN )

Status: done
Back to report list