Detail NR1 ELEC/INST RM/KL/CM
2026-07-23
443-WI1-M3
Wahyu Adi Triono
Problem: Issue over load and motor trip, motor normal function
Action:
Check use megger of R-S-T to ground result 0.4 ohm note inside motor moist hit water from 443 WI1 M2. Install heater lamp at motor 443 WI1 M3 around 10 minutes reconnect cable R-S-T and do megger result 2 mega ohm. Test function motor 443 WI1 M3 result ampere meter 13-14 ( JAJAT & EDI & ADI & UNJ AZRIEL & DADANG )

Status: done